Omron Safety Relays — G7SA

G7SA relays carry forcibly guided contacts to EN/IEC 61810-3, which is what allows a safety contactor stack to be monitored rather than assumed. The guidance means the normally-closed contact cannot physically close if the normally-open contact has not closed first, so a welded contact is detectable. They are relays, not modules — P7SA sockets are separate.

4 SKUs in stock Current production

Lifecycle status

In production — no end-of-life record

Omron carries G7SA with live product pages across Europe and Asia-Pacific and returns no discontinuation entry for the family in its China database. Sockets are the P7SA range and are ordered separately.

What to fit instead: None required

Key specifications

How to read a G7SA model number

The A and B counts are the NO and NC poles. Everything after is the coil.

Element Meaning Example
2A2B 2 NO + 2 NC, four poles G7SA-2A2B DC24
3A1B 3 NO + 1 NC, four poles G7SA-3A1B
5A1B 5 NO + 1 NC, six poles G7SA-5A1B DC24V
DC24 / DC24V Coil voltage 24 VDC

Coil figures differ between the four-pole and six-pole parts: G7SA-2A2B draws roughly 15 mA at 1,600 ohms, while the six-pole G7SA-5A1B is closer to 20.8 mA at 1,152 ohms. Size the safety circuit's supply for the pole count you actually fit.

Where these parts get used

Which model do you need

All 4 Omron Safety Relays SKUs

Every part number below links to its own page with full specifications, compatibility notes and stock status.

Frequently asked

What does forcibly guided contact mean on a G7SA?

It is a mechanical interlock between the normally-open and normally-closed contact sets, certified to EN/IEC 61810-3. The NC contact cannot physically close unless the NO contacts have opened first. That means a welded NO contact is detectable through the NC contact, which is what lets a safety circuit prove the contactor stack actually de-energised instead of assuming it.

What is the difference between G7SA-2A2B and G7SA-5A1B?

Pole count. G7SA-2A2B has 2 normally-open plus 2 normally-closed contacts, four poles and 14 terminals. G7SA-5A1B has 5 normally-open plus 1 normally-closed, six poles. They also differ in coil consumption — the four-pole parts draw roughly 15 mA against about 20.8 mA for the six-pole.

Are G7SA relays a safety relay or a safety relay module?

They are relays with forcibly guided contacts, not modules. The P7SA range is the matching DIN-rail or PCB socket, and it is ordered separately — the G7SA does not come with a base.

How fast is a G7SA?

Operating time 20 ms maximum, response time 10 ms maximum, release time 20 ms maximum. Mechanical durability is 10,000,000 operations minimum and electrical durability 100,000 operations minimum, with a maximum switching frequency of 36,000 operations per hour mechanical or 1,800 per hour at rated load.

Specification sources

Specifications on this page were checked against Omron's own documentation. If a figure here disagrees with your datasheet, the datasheet wins — tell us and we will correct it.